Design: Heating bundle made of stainless steel, protection cage made of painted steel, built-in temperature controller and limiter for monitoring the temperature class horizontal mounting, special design for vertical mounting on request.
Voltage: 230 V AC standard, 110 V ... 690 V AC or 3 phase on request
Type of Protection:
II 2 G EEx de IIC T1...T4, EC type examination certificate PTB 02 ATEX 1085 |

|
| Selection Table |
| type |
temp. class |
power |
voltage |
L1 |
L2 |
weight |
article no. |
| |
|
[W] |
[A] |
[mm] |
[mm] |
[kg] |
|
| DHGSTB1/R-0,5-T4 |
T4 |
500 |
2,2 |
1450 |
1190 |
19 |
204 61 001 |
| DHGSTB1/R-0,75-T4 |
T4 |
750 |
3,3 |
1225 |
965 |
20 |
204 61 002 |
| DHGSTB1/R-1-T4 |
T4 |
1000 |
4,3 |
1450 |
1190 |
21 |
204 61 003 |
| DHGSTB1/R-0,5-T3 |
T3 |
500 |
2,2 |
900 |
640 |
17 |
204 61 004 |
| DHGSTB1/R-0,75-T3 |
T3 |
750 |
3,3 |
1225 |
965 |
18 |
204 61 005 |
| DHGSTB1/R-1-T3 * |
T3 |
1000 |
4,3 |
1450 |
1190 |
19 |
204 61 006 |
| DHGSTB1/R-1,5-T3 |
T3 |
1500 |
6,5 |
1225 |
965 |
20 |
204 61 007 |
| DHGSTB1/R-2-T3 * |
T3 |
2000 |
8,7 |
1450 |
1190 |
21 |
204 61 008 |
| DHGSTB1/R-3-T3 |
T3 |
3000 |
13,0 |
2025 |
1765 |
24 |
204 61 018 |
| DHGSTB1/R-1,5-T2 |
T2 |
1500 |
6,5 |
1450 |
1190 |
19 |
204 61 012 |
| DHGSTB1/R-3-T2 |
T2 |
3000 |
13,0 |
1450 |
1190 |
21 |
204 61 014 |
|
* = types on stock
|
Temperature classes and surface temperatures admitted: T4 < 135°C T3 < 200°C T2 < 300°C |
|